Tell it the load, the voltage and the route length. It works through the cable table and returns the smallest cable, and the fewest parallel runs, that pass all three checks — current rating, voltage drop and short-circuit withstand — with every step of the working shown, ready to print.
| Field | What it is for |
|---|---|
| Project, feeder, from / to | Carried through to the calculation sheet |
| Connected load | In kW, kVA or MVA |
| Power factor and efficiency | Used to convert the load to current |
| Voltage | 230 V single phase, 415 V, 11 kV, 22 kV, 33 kV or 66 kV |
| Standard, core and cable type | Selects the exact cable table — IS 7098, IS 1554 or IS 694; 1 to 4 core; armoured or unarmoured |
| Cable material | Copper or aluminium |
| Cable laid in | Ground, duct or air |
| Derating factor | Automatic for the number of runs, or your own value |
| Length | Route length in metres |
| Permissible voltage drop | Your project limit |
| Fault current and clearing time | For the short-circuit withstand check |
It starts with one run and the smallest size, and steps up until the derated current rating covers the load and the voltage drop is inside your limit. If one run is not enough it tries two, three and four runs.
The minimum size for the fault current and clearing time (adiabatic equation). If that is bigger than the size chosen for load, the cable is upgraded and the working shows why.
Cable tables give three-phase voltage drop. For single-phase circuits the 2/√3 correction is applied automatically, and shown in the working.
It uses the same cable tables as the Voltage and Cable Sizer, so the two applications always agree:
For loads of 750 kW and above it also suggests the bus duct rating to consider instead of cable.
One licence key covers all four applications on one computer. Prices exclude GST.