Auto Cable Sizer

Tell it the load, the voltage and the route length. It works through the cable table and returns the smallest cable, and the fewest parallel runs, that pass all three checks — current rating, voltage drop and short-circuit withstand — with every step of the working shown, ready to print.

What you enter

FieldWhat it is for
Project, feeder, from / toCarried through to the calculation sheet
Connected loadIn kW, kVA or MVA
Power factor and efficiencyUsed to convert the load to current
Voltage230 V single phase, 415 V, 11 kV, 22 kV, 33 kV or 66 kV
Standard, core and cable typeSelects the exact cable table — IS 7098, IS 1554 or IS 694; 1 to 4 core; armoured or unarmoured
Cable materialCopper or aluminium
Cable laid inGround, duct or air
Derating factorAutomatic for the number of runs, or your own value
LengthRoute length in metres
Permissible voltage dropYour project limit
Fault current and clearing timeFor the short-circuit withstand check

What it works out

Smallest cable that passes

It starts with one run and the smallest size, and steps up until the derated current rating covers the load and the voltage drop is inside your limit. If one run is not enough it tries two, three and four runs.

Short-circuit check

The minimum size for the fault current and clearing time (adiabatic equation). If that is bigger than the size chosen for load, the cable is upgraded and the working shows why.

Single phase done properly

Cable tables give three-phase voltage drop. For single-phase circuits the 2/√3 correction is applied automatically, and shown in the working.

Cable data

It uses the same cable tables as the Voltage and Cable Sizer, so the two applications always agree:

For loads of 750 kW and above it also suggests the bus duct rating to consider instead of cable.

What you get out

Use the Auto Cable Sizer on your next job