Plots the time–current curve of every breaker on a fault path — whatever make each one is — on a single graph, and tells you whether they discriminate. Every breaker is set on the real dial steps of its own release, so the settings you print are settings a commissioning engineer can actually enter on site.
Real installations are rarely all one manufacturer. The incomer may be one make, the sub-distribution another and the final boards a third. A manufacturer's own coordination software plots its own range and nothing else — which is exactly the case where discrimination is most likely to be lost. This application carries a release library covering all of them.
| Make | Releases | Covering |
|---|---|---|
| Schneider | 7 | Micrologic 2.2 / 2.3 / 5.0 / 6.0 A-E-P-H, MicroLogic X for MasterPact MTZ, MicroLogic 5.x / 6.x for ComPacT NSX |
| ABB | 13 | Ekip Dip and Ekip Touch / Hi-Touch for Emax 2 and Tmax XT2 / XT4 / XT5 / XT6 / XT7, Tmax T7 |
| Siemens | 17 | 3WL ETU15B to ETU76B, 3WT ETU35WT to ETU47WT, 3WA ETU600, 3VA2 ETU350 / ETU550 / ETU560, SINOVA 3VJ2 |
| Legrand | 8 | DMX3 MP2 / MP4 and DPX3 |
| L&T – Lauritz Knudsen | 8 | U-POWER Omega, Matrix release, D-sine MCCB |
| Generic and any make | 6 | Typical LSIG ranges, MCCB thermal-magnetic, MCB curves B, C and D |
Each release records where its steps came from. A release marked datasheet was checked against the manufacturer's published setting table; partial means the main ranges are from that table and some individual dial steps are typical values; and generic means typical ranges only, to be confirmed before settings are issued. The sources are listed in the report, so a reviewer can see what each curve rests on.
You can pick one make for the whole study at the start, change it later and apply it to every breaker at once — or leave it on All makes and set each breaker individually. Your own releases can be added without touching the program: Release library → Save template writes a JSON file you edit and keep beside the application.
Each protective device is defined by its rating and its trip unit settings. The dials offered are the ones that release actually has, with the steps it actually has, and the curve redraws as you change them:
| Setting | What it controls |
|---|---|
| Ir | Long-time pick-up — the continuous current threshold |
| tr | Long-time delay, at that make's stated reference multiple of Ir |
| Isd | Short-time pick-up — a multiple of Ir on Schneider, of In on ABB |
| tsd | Short-time delay, with I²t switched in or out |
| Ii | Instantaneous pick-up, or OFF, capped at the release's own limit |
| Ig | Earth fault pick-up, as a multiple of In or in amperes |
| tg | Earth fault delay |
The settings you arrive at are printed alongside the graph as a settings sheet, in the form an engineer hands to a commissioning technician.
A breaker does not trip on a line. It trips somewhere inside a band, between the earliest and the latest tripping time allowed by its tolerance. The curves are drawn that way — as bands rather than lines — in the style engineers already read from manufacturers' coordination charts:
For every upstream and downstream pair on the path, the check compares the upstream non-tripping curve against the downstream total clearing curve. That is the strict comparison: the device above must still not have started to operate by the time the device below has finished clearing. Comparing nominal curve against nominal curve can show discrimination that the tolerances then take away.
Discrimination only means something at the fault current that can actually flow at that point in the installation. The Fault Level Study and Earthing Calculator writes a Breaker Settings File; this application reads it, and the fault level at each breaker comes across with it. One click then grades recommended settings along every fault path, from the incomer down, as a starting point you adjust rather than a blank sheet.
Both applications are covered by the same licence key, because in practice neither study is finished without the other.
Tick the formats you want and all three are written at once, each with a MEPDESIGNERSUITE.COM cover page: the settings table, the discrimination check, the release sources, the notes, and every curve followed by its own settings sheet. The Word file is written straight from the Office XML parts, so there is nothing extra to install.
See for yourself what a submission looks like before you subscribe. The same report is below in both formats, exactly as the application wrote it.
One licence key covers all four applications on one computer. Prices exclude GST.